Term Technical data Description
1 Power supply + Auxiliary supply
2 Power supply -
3-4* Status output 2 A @ 35 V
dc
General status output/configurable
Digital input
10 Digital input Remote start/configurable
11 Digital input Remote stop/configurable
12 Digital input Remote alarm ack./configurable
13 Digital input Shutdown override/configurable
14 Digital input Configurable
15 Digital input Configurable
56** Digital input Configurable
57** Digital input Configurable
Output
20 Emergency stop and common for
21 to 23
Common for relay start prepare, starter (crank) and run coil,
and input for emergency stop
21 Relay output 21 Start prepare/configurable, function NO
22 Relay output 22 Starter (crank)/configurable, function NO
23 Relay output 23 Run coil/configurable, function NO
24-25 Relay output 24 Horn/configurable function NO
26-27 Relay output 26 Configurable, function NO
Multi-functional inputs
5 Common Common for term. 6 to 8 and 58 to 59
6 RMI6 4 to 20 mA/binary input Fuel level/configurable
7 RMI7 4 to 20 mA/binary input Oil pressure/configurable
8 RMI8 4 to 20 mA/binary input Water temp./configurable
58** RMI58 4 to 20 mA/resistive/binary
input
● Resistive input or
● 4 to 20 mA from active transducer or
● Binary with wire break
● Pt100
● Pt1000
59** RMI59 4 to 20 mA/resistive/binary
input
● Resistive input or
● 4 to 20 mA from active transducer or
● Binary with wire break
● Pt100
● Pt1000
Tacho RPM input
16 RPM input (MPU) Magnetic pickup/tacho generator
17 RPM-GND Common for RPM input. Internally connected to terminal 2
18 RPM input (W/L) Magnetic pickup. PNP, NPN or charge alternator W term.