Place the cursor under GEN and press ENTER.
Place the cursor under the setting you require and press ENTER.
Generator nominal settings 1
No. Setting Min.
Max.
Factory
setting
Notes Ref. Description
6000 Nominal settings 1
6001 Nom. set-
tings 1
Frequen-
cy
48.0 Hz
62.0 Hz
50.0 Hz Designer's
Reference
Handbook
The selection of nominal
settings to be used is set
in 6006. A binary input or
selection in M-Logic can
also be used.
The range of nom. volt-
age and nom. power de-
pends on the selected
range in "9030 Scaling".
6002 Nom. set-
tings 1
Power 10 kW
20000 kW
480 kW
6003 Nom. set-
tings 1
Current 0 A
9000 A
867 A
6004 Nom. set-
tings 1
Voltage 100 V
25000 V
400 V
6005 Nom. set-
tings 1
RPM 100 RPM
4000 RPM
1500
RPM
6006 Nom. set-
tings 1
Set 1
4
1
To adjust the transformer settings, use the or push-button to get to the transformer page.
ML-2 quick start guide 4189340603 UK
The first steps
DEIF A/S Page 16 of 23