Optics removal
Remove an optic by pushing the tab on the optic and sliding the optic from the port.
When removing optics with direct attach cables (DACs) from the port, pull the release tab
rmly and steadily. Before pulling the release tab, you may need to gently push the optic into
the port to ensure that it is seated properly. Do not jerk or tug repeatedly on the tab.
Switch power-up
Supply power to the S5200F-ON Series switch after you mount it in a rack or cabinet.
Reinspect your switch before power up. Verify the following:
• The equipment is properly secured to the rack. Dell EMC recommends properly
grounding the switch.
• The ambient temperature around the unit, which may be higher than the room
temperature, is within the limits specied for the S5200F-ON Series switch, see
Specications.
• There is sucient airow around the unit.
• The input circuits are correctly sized for the loads and that you use sucient
overcurrent protection devices.
• All protective covers are in place.
CAUTION
: Do not power up the switch if you did not install a fan module.
NOTE: A US AC power cable is included for powering up an AC power supply. You
must order all other power cables separately.
NOTE: ESD damage can occur if components are mishandled. Always wear an ESD-
preventive wrist or heel ground strap when handling the switch and its components.
Power up sequence
When the switch powers up, the fans immediately come on at high speed. The fan speed
slows as the switch continues to boot up.
S5200F-ON Series switch Installation
37