EasyManua.ls Logo

Dell iDRAC 8 - Configuring Power Supply Options

Dell iDRAC 8
309 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuring power cap policy using web interface
To view and configure the power policies:
1.
In iDRAC Web interface, go to OverviewServerPower/ThermalPower ConfigurationPower Configuration. The
Power Configuration page is displayed.
The Power Configuration page is displayed. The current power policy limit is displayed under the Currently Active Power Cap
Policy section.
2. Select Enable under iDRAC Power Cap Policy.
3. Under User-Defined Limits section, enter the maximum power limit in Watts and BTU/hr or the maximum % of recommended
system limit.
4. Click Apply to apply the values.
Configuring power cap policy using RACADM
To view and configure the current power cap values, use the following objects with the set command:
System.Power.Cap.Enable
System.Power.Cap.Watts
System.Power.Cap.Btuhr
System.Power.Cap.Percent
For more information, see the iDRAC RACADM Command Line Interface Reference Guide available at dell.com/idracmanuals.
Configuring power cap policy using iDRAC settings utility
To view and configure power policies:
1. In iDRAC Settings utility, go to Power Configuration.
NOTE: The Power Configuration link is available only if the server power supply unit supports power monitoring.
The iDRAC Settings Power Configuration page is displayed.
2. Select Enabled to enable the Power Cap Policy Else, select Disabled.
3. Use the recommended settings, or under User Defined Power Cap Policy, enter the required limits.
For more information about the options, see the iDRAC Settings Utility Online Help.
4. Click Back, click Finish, and then click Yes.
The power cap values are configured.
Configuring power supply options
You can configure the power supply options such as redundancy policy, hot spare, and power factor correction.
Hot spare is a power supply feature that configures redundant Power Supply Units (PSUs) to turn off depending on the server load.
This allows the remaining PSUs to operate at a higher load and efficiency. This requires PSUs that support this feature, so that it
quickly powers ON when needed.
In a two PSU system, either PSU1 or PSU2 can be configured as the primary PSU. In a four PSU system, you must set the pair of
PSUs (1+1 or 2+2) as the primary PSU.
After Hot Spare is enabled, PSUs can become active or go to sleep based on load. If Hot Spare is enabled, asymmetric electrical
current sharing between the two PSUs is enabled. One PSU is awake and provides the majority of the current; the other PSU is in
sleep mode and provides a small amount of the current. This is often called 1 + 0 with two PSUs and hot spare enabled. If all PSU-1s
are on Circuit-A and all PSU-2s are on Circuit-B, then with hot spare enabled (default hot spare factory configuration), Circuit-B has
much less load and triggers the warnings. If hot spare is disabled, the electrical current sharing is 50-50 between the two PSUs, the
Circuit-A and Circuit-B normally has the same load.
171

Table of Contents

Related product manuals