Operating temperature +10° to +35° C (50° to 95° F) with a maximum
temperature gradation of 10° per hour .
Note: for Altitudes above 2950 feet , the maximum
operating temperature is de-rated 1°F/550ft.
All temperature ratings shown are for sea level. An
altitude de-rating of 1°C per 300 m (1.8°F per 1,000
ft) to 3048 m (10,000 ft) is applicable. No direct
sunlight allowed.
Shipping temperature -30°C to 50°C (-22°F to 122°F)
Storage temperature -30°C to 60°C (-22°F to 140°F)
Maximum wet bulb
temperature
28°C (82.4°F)
ATTENTION
All temperature ratings described
previously are for sea level. An altitude
derating of 1°C per 300 m (1.8°F per 1,000
ft) to 3048 m (10,000 ft) is applicable. Direct
sunlight is not allowed.
Operating humidity 20% to 80% (non-condensing) with a maximum
humidity gradation of 10% per hour
Storage humidity 5% to 95% (non-condensing) ) with a maximum
humidity gradation of 10% per hour
ATTENTION
Storing maximum humidity of 95% is based
on a maximum temperature of 45°C
(113°F). Altitude maximum for storage
corresponds to a pressure minimum of 70
KPa.
Airborne Contaminants Airborne Contaminants < 300 angstroms/month
Copper Reactivity Level Copper Reactivity Level < 3 mm3/m3 parts per billion
H2S Gas concentration H2S Gas concentration < 10 mm3/m3 parts per
billion
S02, S03 Gas concentration S02, S03 Gas concentration < 1 mm3/m3 parts per
billion
CI2 Gas concentration CI2 Gas concentration < 50 mm3/m3 parts per billion