Temperature Specications
Storage –40°C to 65°C (–40°F to 149°F)
Continuous
operation (for
altitude less than
950 m or 3117 ft)
10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment.
Fresh air For information on fresh air, see Expanded Operating Temperature section.
Maximum
temperature
gradient (operating
and storage)
20°C/h (68°F/h)
Relative humidity Specications
Storage 5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be non-condensing at all times.
Operating 10% to 80% Relative Humidity with 29°C (84.2°F) maximum dew point.
Maximum
vibration
Specications
Operating 0.26 G
rms
at 5 Hz to 350 Hz (operation orientation).
Storage 1.88 G
rms
at 10 Hz to 500 Hz for 15 min (all six sides tested).
Maximum shock Specications
Operating Six consecutively executed shock pulses in the positive and negative x, y, and z axes of 40 G for up to 2.3
ms.
Storage Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side
of the system) of 71 G for up to 2 ms.
Maximum
altitude
Specications
Operating
3048 m (10,000 ft).
Storage 12,000 m (39,370 ft).
Operating
temperature de-
rating
Specications
Up to 35 °C (95 °F) Maximum temperature is reduced by 1°C/300 m (33.8°F/984.25 ft) above 950 m (3,117 ft)
The following section denes the limits to help avoid IT equipment damage and/or failure from particulates and gaseous
contamination. If the levels of particulates or gaseous pollution are beyond the specied limits and cause equipment damage or
failure, you may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the
customer.
Particulate
contamination
Specications
Air ltration Data center air ltration as dened by ISO Class 8 per ISO 14644-1 with a 95% upper condence limit.
29