Particulate
contamination
Specications
NOTE: Applies to data center environments only. Air ltration requirements do not apply to IT
equipment designed to be used outside a data center, in environments such as an oce or factory
oor.
NOTE: Air entering the data center must have MERV11 or MERV13 ltration.
Conductive dust Air must be free of conductive dust, zinc whiskers, or other conductive particles.
NOTE: Applies to data center and non-data center environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE: Applies to data center and non-data center environments.
Gaseous
contamination
Specications
Copper coupon
corrosion rate
<300 Å/month per Class G1 as dened by ANSI/ISA71.04-1985.
Silver coupon
corrosion rate
<200 Å/month as dened by AHSRAE TC9.9.
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
30