Q What is the maximum output frequency with the 599Hz limitation?
A - In VF Mode the maximum output frequency is 599Hz.
- In SVC or Vector Mode the maximum output frequency, including slip compensation,
is 599Hz. Therefore the max frequency command is 599Hz-Slip !
- In FOC mode (C2000) , the max frequency command is limited to (F
set
+ Pr10-
29)≤599Hz, to make sure the actual output frequency is limited to 599.00Hz.
Q When using a Profibus card how do I change the Baud rate? Do I need to make
any changes in the Menu 9 parameters?
A No, the transmission speed is only set in the master configuration (as shown below)
and the Profibus slave card will auto-detect the speed.
Q What power cable section to use?
A We often get questions about the power cable cross section that is needed in an
application and the relevant info in the user manuals.
In our user manuals, we state the cable cross section that the power terminals can
accommodate. It doesnt mean you always have to use the indicated cable.
Example: ME300 Frame B