16
Infrasuite Power Management
No. Item Description
5
DIP
Switches
Set up operation mode. Please refer to the following table.
1 2
ON
DIP Switch 2DIP Switch 1
DIP
Switch 1
DIP
Switch 2
Operation
Mode
Description
OFF OFF
Normal
Mode
The built-in SNMP IPv6
provides the STS’s
status information and
parameters through a
network system.
OFF ON
Pass
Through
Mode
The built-in SNMP
IPv6 stops polling
the STS but transfers
the communication
data between the
LOCAL port and
the STS. ModBus
Communication:
9600bps 8-N-1.
ON OFF N/A Invalid state.
ON ON
Congura-
tion Mode
In this mode, user
can login through
the LOCAL port and
congure the built-in