Chapter 7 InsightPower SNMP IPv6 for STS
29
Command Description Parameter Response
SetDevID Set the unit's device ID. <20
characters>
alphanumeric
only
Various kinds
SetVtp2s Set the primary to secondary
trip voltage.
165.0 ~ 175.0 Various kinds
SetVts2p Set the secondary to primary
trip voltage.
165.0 ~ 175.0 Various kinds
SetVbp2s Set the primary to secondary
brownout voltage.
180.0 ~ 264.0 Various kinds
SetVbs2p Set the secondary to primary
brownout voltage.
180.0 ~ 264.0 Various kinds
SetTdp2s Set the recover time of
transfer from primary to
secondary.
12.0 ~ 1800.0 Various kinds
SetTds2p Set the recover time of
transfer from secondary to
primary.
12.0 ~ 1800.0 Various kinds
SetMvs1 Set the max voltage of
comparing cycles for primary
AC blackout.
30 ~ 50 Various kinds
SetMvs2 Set the max voltage of
comparing cycles for
secondary AC blackout.
30 ~ 50 Various kinds
SetMts1 Set the max time of
comparing cycles for primary
AC blackout.
2.0 ~ 4.0 Various kinds
SetMts2 Set the max time of
comparing cycles for
secondary AC blackout.
2.0 ~ 4.0 Various kinds
UpProcess Status of upgrade progress. N/A Idle / Run / Error
UpStep Stage of upgrade progress. N/A Init / File ID / Auth
/ Addr / Erase /
Program / Read