28
Infrasuite Power Management
Command Description Parameter Response
Tds2p Report the recover time of
transfer from secondary to
primary.
N/A
#.#
Mvs1 Report the max voltage of
comparing cycles for primary
AC blackout.
N/A #.#
Mvs2 Report the max voltage
of comparing cycles for
secondary AC blackout.
N/A #.#
Mts1 Report the max time of
comparing cycles for primary
AC blackout.
N/A #.#
Mts2 Report the max time of
comparing cycles for
secondary AC blackout.
N/A #.#
Log Report the event code and
time of prior transfers.
1 ~ 10 hh:mm:ss MM/DD/
YYYY 0x#
Tprev[1..9] Report the time of prior
transfer/event.
Tprev1 is the most recent
time.
N/A hh:mm:ss MM/DD/
YYYY
Event[1..9] Report the event code for
prior transfer.
Event1 is the most recent
event.
N/A 0x#
ClearLog Clear event log. N/A Various kinds
SetTime Set the present time. hh:mm:ss
[MM/DD/
YYYY]
Various kinds
SetDate Set the present date. MM/DD/YYYY Various kinds
SetPrefer Set the preferred source. 1 or 2 Various kinds