Chapter 4 Parameters|   
Revision May 2008, ME14, SW V3.04  4-31
 
Input
Power 
Allowable Max. Power Loss Time
Output
Power
Output
Voltage
Pr.33
Speed search starts with
the Master Frequency
Pr.32=1
Baseblock
Time
Pr.34
speed synchronization
detection
speed search
Allowable Max. power loss time
Pr.33
Speed search starts with
minimum output frequency
Pr.32=2
Baseblock
Time
Pr.34
 
 
Pr.36 
Upper Bound of Output Frequency 
Unit: 0.1Hz
  Settings  0.10 Hz to 400.0 Hz  Factory Setting: 400
  The Upper/Lower Bounds help prevent operation error and machine damage.  
  If the Upper Bound of Output Frequency is 50Hz and the Maximum Output Frequency is 60Hz, 
the Maximum Output Frequency will be limited to 50Hz. 
  Setting of this parameter must be equal to or greater than the Lower Bound of Output 
Frequency (Pr.37). 
 
Pr.37 
Lower Bound of Output Frequency 
Unit: 0.1Hz
  Settings  0.00 Hz to 400.0 Hz  Factory Setting: 0 Hz
  Setting of this parameter must be equal to or less than the Upper Bound of Output Frequency 
  If the Lower Bound of Output Frequency is 10Hz, and the Minimum Output Frequency (Pr.08) 
is set at 1.0Hz, then any command frequency between 1-10Hz will generate a 10Hz output 
from the drive. 
 
output frequency
Pr.36
Pr.37
Input Freq.