ASDA-A2  Chapter 8  Parameters 
Revision February, 2017    8-149 
P4-04★ 
 
ASH5  Fault Record (N-4) 
Address: 0408H 
0409H 
 
Operational 
Interface: 
Panel / Software  Communication 
Related Section: 
4.4.1 
 
Default: 
0 
 
Control 
Mode: 
ALL 
 
Unit: 
- 
 
Range: 
- 
 
Data Size: 
32-bit 
 
Format: 
Hexadecimal 
 
Settings: 
The last fifth abnormal status record 
Low word: LXXXX: display ALM number 
High word: hYYYY: display the error code corresponds to CANopen / 
DMCNET 
 
P4-05    JOG  Servo Motor Jog Control 
Address: 040AH 
040BH 
 
Operational 
Interface: 
Panel / Software  Communication 
Related Section: 
4.4.2 
 
Default: 
20 
 
Control 
Mode: 
ALL 
 
Unit: 
r/min 
 
Range: 
0 ~ 5000 
 
Data Size: 
16-bit 
 
Format: 
Decimal 
 
Settings: 
Three control methods are as follows: 
1. Operation Test 
After the JOG speed is set by P4-05 via panel, the panel will 
display the symbol of JOG. Pressing the UP Key can control JOG 
operation in positive direction, pressing the DOWN Key can control 
negative direction. Stop pressing to stop the JOG operation. If 
there is any error in this setting, then the motor cannot operate. 
The maximum JOG speed is the maximum speed of the servo 
motor. 
2. DI Control 
If the DI is set to JOGU and JOGD (refer to table 8.1), then the 
JOG operation in positive or negative direction can be controlled 
via this DI.