28
Alarm - Over Apparent Power Demand
A4 Alarm Enable
0: Disable
1: Enable
byte 1 R / W
A5
pickup setpoint (apparent power
demand exceeds this value
(kVA), alarm generated)
0.000~99999.999 Float kVA 4 R / W
A6
A7
pickup time delay (triggering
delayed)
0~99 byte s 2 R / W
A8
dropout setpoint (apparent power
lower than this value (kVA), alarm
cleared)
0.000~99999.999 Float kVA 4 R / W
A9
AA
dropout time delay (restoration
delayed)
0~99 byte s 2 R / W
Alarm - Over Frequency
AB Alarm Enable
0: Disable
1: Enable
byte 1 R / W
AC
pickup setpoint (frequency
exceeding this value (Hz), alarm
generated)
0.000~99999.999 Float Hz 4 R / W
AD
AE
pickup time delay (triggering
delayed)
0~99 byte s 2 R / W
AF
dropout setpoint (frequency
lower than this value (Hz), alarm
cleared)
0.000~99999.999 Float Hz 4 R / W
B0
B1
dropout time delay (restoration
delayed)
0~99 byte s 2 R / W
Alarm - Under Frequency
B2 Alarm Enable
0: Disable
1: Enable
byte 1 R / W
B3
pickup setpoint (frequency
lower than this value (Hz), alarm
generated)
0.000~99999.999 Float Hz 4 R / W
B4
B5
pickup time delay (triggering
delayed)
0~99 byte s 2 R / W
B6
pickup setpoint (frequency
exceeding this value (Hz), alarm
generated)
0.000~99999.999 Float Hz 4 R / W
B7
B8
dropout time delay (restoration
delayed)
0~99 byte s 2 R / W
Alarm - Over Voltage THD
B9 Alarm Enable
0: Disable
1: Enable
byte 1 R / W
BA
pickup setpoint (voltage THD
exceeding this value, alarm
generated)
0.000~99999.999 Float % 4 R / W
BB
BC
pickup time delay (triggering
delayed)
0~99 byte s 2 R / W
BD
dropout setpoint (voltage THD
lower than this value (kW), alarm
cleared)
0.000~99999.999 Float % 4 R / W
BE
BF
dropout time delay (restoration
delayed)
0~99 byte s 2 R / W
Alarm - Over Current THD
C0 Alarm Enable
0: Disable
1: Enable
byte 1 R / W