- 10 -
Address
Content
Explanation
1030H
Start pattern number
0 ~ 7
1032H
Read program Step time left (second)
1033H
Read program Step time left (minute)
1034H
Read present executing program step
number
1035H
Read present executing program pattern
number
1036H
Read program dynamic set value
1040H~
1047H
Actual step number setting inside the
correspond pattern
0 ~ 7 = N, indicate that this pattern is executed from step 0 to step N
1050H~
1057H
Cycle number for repeating the execution of the
correspond pattern
0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times
1060H~
1067H
Link pattern number setting of the correspond
pattern
0 ~ 8, 8 indicates the program end. 0~7 indicates the next execution pattern
number after executing the current pattern
2000H~
203FH
Pattern 0~7 temperature set point setting
Pattern 0 temperature is set to 2000H ~ 2007H
-999 ~ 9,999
2080H~
20BFH
Pattern 0~7 execution time setting
Pattern 0 time is set to 2080H~2087H
Time 0 ~ 900 (1 minute per scale)
6.
Address and Content of Bit Register: (First bit of reading will put into LSB, Write data = FF00H for bit set, 0000H for bit clear)
Address
Content
Explanation
0800H
Read AT LED status
0:OFF; 1: ON
0801H
Read Output 1 LED status
0: OFF; 1:ON
0802H
Read Output 2 LED status
0:OFF; 1: ON
0803H
Read Alarm 1 LED status
0: OFF; 1:ON
0804H
Read
o
F LED status
0: OFF; 1: ON
0805H
Read
o
C LED status
0: OFF; 1: ON
0806H
Read Alarm 2 LED status
0: OFF; 1: ON
0807H
Read Alarm 3 LED status
0: OFF; 1: ON
0808H
Read SET key status
0: Press down
0809H
Read FUNCTION key status
0: Press down
080AH
Read UP key status
0: Press down
080BH
Read DOWN key status
0: Press down
080CH
Read Event 1 status
1: Event action
080DH
Read Event 2 status
1: Event action
080EH
Read System Alarm status
1: Alarm action
0810H
Communication write-in selection
Communication write in disabled: 0 (default), Communication write in
enabled: 1
0811H
Temperature unit display selection
o
C/linear input (default): 1;
o
F: 0
0812H
Decimal point position selection
Except for the thermocouple B, S, R type, all the other thermocouple type are
valid. (0 or 1)
0813H
AT setting
OFF: 0 (default), ON : 1
0814H
Control RUN/STOP setting
0: STOP, 1: RUN (default)
0815H
STOP setting for PID program control
0: RUN (default), 1: STOP
0816H
Temporarily STOP for PID program control
0: RUN (default), 1: Temporarily STOP
0817H
Valve feedback setting status
0: w/o feedback (default), 1: feedback function
0818H
Auto-tuning valve feedback status
0: Stop AT (default), 1: Start AT
7.
Communication Transmission Format: Command Code: 02: read N bits, 05: write 1 bit, 03: read N words, 06: write 1 word.