- 9 -
Address
Content
Explanation
8006H : Cannot get temperature value, ADC input error
8007H : Memory read/write error
1001H
Set point (SV)
Unit is 0.1,
o
C or
o
F
1002H
Upper-limit of temperature range
The data content should not be higher than the temperature range
1003H
Lower-limit of temperature range
The data content should not be lower than the temperature range
1004H
Input temperature sensor type
Please refer to the contents of the “Temperature Sensor Type and Temperature
Range” for detail
1005H
Control method
0: PID, 1: ON/OFF, 2: manual tuning, 3: PID grogram control
1006H
Heating/Cooling control selection
0: Heating, 1: Cooling, 2: Heating/Cooling, 3: Cooling/Heating
1007H
1st group of Heating/Cooling control cycle
0 ~ 99, 0:0.5 sec
1008H
2nd group of Heating/Cooling control cycle
0 ~ 99, 0:0.5 sec
1009H
PB Proportional band
0.1 ~ 999.9
100AH
Ti Integral time
0 ~ 9,999
100BH
Td Derivative time
0 ~ 9,999
100CH
Integration default
0 ~ 100%, unit is 0.1%
100DH
Proportional control offset error value, when Ti
= 0
0 ~ 100%, unit is 0.1%
100EH
The setting of COEF when Dual Loop output
control are used
0.01 ~ 99.99
100FH
The setting of Dead band when Dual Loop
output control are used
-999 ~ 9,999
1010H
Hysteresis setting value of the 1st output group
0 ~ 9,999
1011H
Hysteresis setting value of the 2nd output group
0 ~ 9,999
1012H
Output value read and write of Output 1
Unit is 0.1%, write operation is valid under manual tuning mode only.
1013H
Output value read and write of Output 2
Unit is 0.1%, write operation is valid under manual tuning mode only.
1014H
Upper-limit regulation of analog linear output
1 Unit = 2.8uA (Current Output) = 1.3mV (Linear Voltage Output)
1015H
Lower-limit regulation of analog linear output
1 Unit = 2.8uA (Current Output) = 1.3mV (Linear Voltage Output)
1016H
Temperature regulation value
-999 ~ +999, unit: 0.1
1017H
Analog decimal setting
0 ~ 3
1018H
Time for valve from full open to full close
0.1 ~ 999.9
1019H
Dead Band setting of valve
0 ~ 100%; unit: 0.1%
101AH
Upper-limit of feedback signal set by valve
0 ~ 1,024
101BH
Lower-limit of feedback signal set by valve
0 ~ 1,024
101CH
PID parameter selection
0 ~ 4
101DH
SV value corresponded to PID value
Only valid within available range, unit: 0.1 scale
1020H
Alarm 1 type
Please refer to the contents of the “Alarm Outputs” for detail
1021H
Alarm 2 type
Please refer to the contents of the “Alarm Outputs” for detail
1022H
Alarm 3 type
Please refer to the contents of the “Alarm Outputs” for detail
1023H
System alarm setting
0 : None (default), 1~3 : Set Alarm 1 to Alarm 3
1024H
Upper-limit alarm 1
Please refer to the contents of the “Alarm Outputs” for detail
1025H
Lower-limit alarm 1
Please refer to the contents of the “Alarm Outputs” for detail
1026H
Upper-limit alarm 2
Please refer to the contents of the “Alarm Outputs” for detail
1027H
Lower-limit alarm 2
Please refer to the contents of the “Alarm Outputs” for detail
1028H
Upper-limit alarm 3
Please refer to the contents of the “Alarm Outputs” for detail
1029H
Lower-limit alarm 3
Please refer to the contents of the “Alarm Outputs” for detail
102AH
Read LED status
b0 : Alm3, b1: Alm2, b2: F, b3:
℃
, b4: Alm1, b5: OUT2, b6: OUT1, b7: AT
102BH
Read pushbutton status
b0 : Set, b1 : Select, b2 : Up, b3 : Down. 0 is to push
102CH
Setting lock status
0 : Normal, 1 : All setting lock, 11 : Lock others than SV value
102DH
CT read value
Unit: 0.1A
102FH
Software version
V1.00 indicates 0x100