DVP-ES2/EX2/EC5/SS2/SA2/SX2/SE&TP Operation Manual - Programming
Contents:
1. M1037 and D1037 can be used to enable 8 sets of SPD instructions. When M1037 is ON, 8
sets of SPD instructions will be enabled. When M1037 is OFF, the function will be disabled.
2. Availability:
3. The detected speed will be stored in the registers designated by D1037, e.g. if D1037 = K100,
the user has to set up the value in D100, indicating the interval for capturing the speed value
(unit: ms). In addition, the captured speed value will be stored in D101 ~ D108 in order.
※ When the function is enabled, C235~C242 will be occupied and unavailable in PLC
execution process program.
ZRST C235 C242
M1002
MOV K100 D1037
MOV K1000 D100
M1037
M1
K10000 K0 Y0
M1000
PLSY
K9000 K0 Y1
M1000
PLSY
K8000 K0 Y2
M1000
PLSY
K7000 K0 Y3
M1000
PLSY
END
Communication Response Delay
Contents:
1. Data response delay time can be set when PLC is a Slave in COM2, COM3 RS-485
communication. Unit: 0.1ms. 0~10,000 adjustable.
2. For the following models and firmware versions, the setting range is 0-20.
Model
/ES2-C
EC5 ES2-E
SX2
SS2 12SE 26SE 28SA2
V3.64 V1.00 V1.40 V3.00 V3.60 V1.86 V1.40 V3.00
3. By using PLC-Link, D1038 can be set to send next communication data with delay. Unit: 1 scan
cycle. 0~10,000 adjustable
Model ES2/EX2
ES2-C ES2-E 12SA2
SX2 SS2 12SE 26SE 28SA2
V1.42 V3.00 V1.08 V2.60
V2.40 V3.28 V2.02 V1.00 V2.90