EasyManua.ls Logo

Delta DVP-SS2 - Page 419

Delta DVP-SS2
1006 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DVP-ES2/EX2/EC5/SS2/SA2/SX2/SE&TP Operation Manual - Programming
3-298
Device No.
Function
Set-point range
Explanation
S
3
+17, 18 The previous PV, 32-bit
-2,147,483,648~
2,147,483,647
The previous PV is usually for
reference. Users can clear or
modify it according to specific
needs.
S
3
+19, 20
For system use only.
12. The explanation of 32-bit S
3
and 16-bit S
3
are almost the same. The difference is the capacity
of S
3
+5 ~ S
3
+20.
PID Equations:
1. When control mode (S
3
+4) is selected as K0, K1, K2 and K5:
In this control mode, PID operation can be selected as Automatic, Forward, Reverse and
Automatic with MV upper/lower bound control modes. Forward / Reverse direction is
designated in S
3
+4. Other relevant settings of PID operation are set by the registers
designated in S
3
~
S
3
+5.
PID equation for control mode k0~k2:
( ) ( )
( )
StPVK
S
tEKtEKMV
DIP
*
1
** ++=
where
MV
: Output value
P
K
: Proprotional gain
( )
tE
: Error value
PV
(t): Present measured value
SV
(t): Target value
D
K
: Derivative gain
( )
StPV
: Derivative value of PV(t)
I
K
: Integral gain
( )
S
tE
1
: Integral value of E(t)
When
( )
tE
is smaller than 0 as the control mode is selected as forward or inverse,
( )
tE
will be regarded as “0"
Control mode
PID equation
Forward, automatic
E(t) = SV PV
Inverse
E(t) = PV SV
Control diagram:
In diagram below, S is derivative operation, referring to “(PVprevious PV) ÷ sampling
time”. 1 / S is integral operation, referring to “previous integral value + (error value ×
sampling time)”. G(S) refers to the device being controlled.

Table of Contents

Other manuals for Delta DVP-SS2

Related product manuals