EasyManua.ls Logo

Delta DVP-SS2 - Page 423

Delta DVP-SS2
1006 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DVP-ES2/EX2/EC5/SS2/SA2/SX2/SE&TP Operation Manual - Programming
3-302
Step1:
Set K
I
and K
D
as 0, and K
P
as 5, 10, 20, 40. Record the SV and PV respectively and the results are
as the figure below.
1.5
1
0.5
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
K =40
P
K =20
P
K =10
P
SV=1
K =5
P
Time (sec)
Step 2:
When K
P
is 40, response overshoot occurs, so we will not select it.
When K
P
is 20, PV response is close to SV and won’t overshoot, but transient MV will be to large
due to a fast start-up. We can put it aside and observe if there are better curves.
When K
P
is 10, PV response is close to SV and is smooth. We can consider using it.
When K
P
is 5, the response is too slow. So we won’t use it.
Step 3:
Select K
P
= 10 and increase K
I
gradually, e.g. 1, 2, 4, 8. K
I
should not be bigger than K
P
. Then,
increase K
D
as well, e.g. 0.01, 0.05, 0.1, 0.2. K
D
should not exceed 10% of K
P
. Finally we obtain
the figure of PV and SV below.
1.5
1
0.5
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
PV=SV
K =10,K =8,K =0.2
P I D
Time (sec)
Note: The example is only for reference. Users have to adjust parameters according to the
condition of the actual control system.

Table of Contents

Other manuals for Delta DVP-SS2

Related product manuals