3. Instruction Set
3-407
API
Mnemonic Operands Function
Controllers
ES2/EX2/
EC5
SS2
SA2
SE
SX2
111 D
EZCP P
Floating point zone
compare
Type
OP
Bit Devices Word devices Program Steps
X Y M S K H KnX
KnY
KnM
KnS
T C D E F
DEZCP, DEZCPP: 17
steps
S
1
*
*
*
S
2
*
*
*
S
*
*
*
D
*
*
*
PULSE
16-bit
32-bit
ES2/EX2/
EC5
SS2
SA2
SE
SX2
ES2/EX2/
EC5
SS2
SA2
SE
SX2
ES2/EX2/
EC5
SS2
SA2
SE
SX2
Operands:
S
1
: Lower bound of zone comparison S
2
: Upper bound of zone comparison S: Comparison
value D: Comparison result, 3 consecutive devices
Explanations:
1. The data of S is compared to the data range of S
1
~ S
2
and the result (, , ) is indicated by
three bit devices in D.
2. If the source operand S
1
or S
2
is specified as constant K or H, the integer value will
automatically be converted to binary floating point for comparison.
3. Operand S
1
should be smaller than operand S
2.
When S
1
> S
2
, the instruction takes S
1
as the 1
st
comparison value and performs normal comparison similar to ECMP instruction.
Program Example:
1. If the specified device is M10, M10~M12 will automatically be used.
2. When X0 = ON, one of M10~M12 will be ON. When X0 = OFF, DEZCP instruction is not
executed, M10~M12 will retain their previous state before X0 = OFF.
3. RST or ZRST instruction is required if users need to reset the comparison result.
X0
DEZCP D0 D10 D20
M10
M11
M12
M10 = ON when (D1,D0)>(D21,D20)
M11 = ON when (D1,D0) (D21,D20) < (D11,D10)
<
M12 = ON when (D21 D20)>(D11,D10)
,