DVP-ES2/EX2/EC5/SS2/SA2/SX2/SE&TP Operation Manual - Programming
4-10
An example of exception response of command code 01H and exception 02H:
Sent message:
Field Name
Example (Hex)
START
No data input
≥
10 ms
Slave Address
01
Command code
01
Starting Address
04
00
Number of Points
00
10
CRC CHK Low
3C
CRC CHK High
F6
END
No data input
≥
10 ms
Feedback message:
Field Name
Example (Hex)
START
No data input
≥
10 ms
Slave Address
01
Function
81
Exception Code
02
CRC CHK Low
C1
CRC CHK High
91
END
No data input
≥
10 ms