EasyManua.ls Logo

Delta DVP02LC-SL - Page 24

Delta DVP02LC-SL
38 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Load Cell Module DVP02LC-SL
DVP-PLC Operation Manual
22
Characteristic Value/Measurement time
y Characteristic value: The eigenvalue, corresponding to the value set in CR#2. Scroll down to
select 1, 2, 4 or 6 mV/V. The default setting is 2 mV/V.
y Measurement time: Corresponds to the value set in CR#3. Scroll down to select 2, 10, 20, 40
or 80 ms. The default setting is 80 ms.
RS-232 Communication
y Station address: The node address, corresponding to the value set in CR#52. The range is 1
to 255, and the default setting is 1.
y Baud rate: Corresponds to bit4 to bit7 of CR#53. Scroll down to select 9600, 19200, 38400,
57600 or 115200. The default setting is 9600.
y Transfer mode: The transmission mode, corresponding to bit15 of CR#53. Scroll down to
select RTU or ASCII. The default setting is ASCII.
y Data length: Corresponds to bit3 of CR#52. Scroll down to select 7 or 8. The default setting is
7. When the transmission mode is set to be RTU, the data length will be automatically set to
8.
y Parity: Corresponds to bit0 to bit1 of CR#53. Scroll down to select none, odd or even. The
default setting is even.
y Stop bit: Corresponds to bit2 of CR#53. Scroll down to select 0 or 1. The default setting is 1.