Chapter 9 SpecificationsMS300
180
230V models one-phase
Frame
B
C
Model VFD_ _ _ _ _ _ _ _AA
4A8MS21AFS
7A5MS21_ _ _
11AMS21_ _ _
ANS
ENS
AFS
ANS
ENS
AFS
Applicable Motor Output (kW)
0.75
1.5
2.2
Applicable Motor Output (HP)
1
2
3
Outp
ut*
Heavy Duty
Rated Output Capacity (kVA)
1.8
2.9
4.2
Rated Output Current (A)
4.8
7.5
11
Carrier Frequency (kHz)
2–15 (Default: 4)
Normal Duty
Rated Output Capacity (kVA)
1.9
3.2
4.8
Rated Output Current (A)
5
8.5
12.5
Carrier Frequency (kHz)
2–15 (Default: 4)
Input
Rated Input
Current (A)
Heavy Duty
10.8
16.5
24.2
Normal Duty
11.3
18.5
27.5
Rated Voltage / Frequency
One-phase 200240 V
AC
(-1510%), 5060 Hz
Mains Input Voltage Range (V
AC
)
170265
Mains Frequency Range (Hz)
4763
Weight (kg)
1.32
1.24
1.8
1.24
1.8
Cooling Method
Fan cooling
EMC Filter
Built-in
Optional
Built-in
Optional
Built-in
IP Rating
IP20
IP40*
IP20
IP40*
IP20
Table 9-3
NOTE:
1. Output*: Default is heavy duty.
2. IP40*: The IP ratings of the wiring area (main circuit terminals and control terminals for frame A/B/C/D/E/F)
and the vent near the capacitor (frame C/D/E/F) are both IP20.
3. The value of the carrier frequency is a factory default. Decrease the current value if you need to increase the
carrier frequency. Refer to Section 9-7 Derating for Ambient Temperature and Altitude for details.
4. For shock or impact load applications, select a drive with a larger capacity model.