22
Installation guide for solar inverters RPI M6A M8A M10A EU V5 EN 2022-08-15
Commissioning – further settings (optional)
Date and time
E-Today: 0kWh
Power: 0W
Status: On Grid
12.Sep 2019 15:32
1. If the default information is displayed, press the
ESC
button to open the main
menu. Otherwise, press the
ESC
button repeatedly until the main menu is
displayed.
Inverter Info.
General Settings
Install Settings
2. Use the and buttons to select the General Settings entry and then
press the
ENT
button.
Baud rate
Date & Time
3. Press the and buttons to select the entry Date and Time and press
the
ENT
button.
10.Sep 2019 14:55
4. Use the and buttons to congure the value and then press the
ENT
button.
Repeat the procedure for the other settings.
Inverter ID
If multiple inverters are connected to the PV system, a dierent inverter ID must set for each inverter. The
inverter ID is used, for example, by monitoring systems to uniquely identify each inverter.
Status: On Grid
12.Sep 2019 15:32
1. If the default information is displayed, press the
ESC
button to open the main
menu. Otherwise, press the
ESC
button repeatedly until the main menu is
displayed.
Inverter Info.
General Settings
Install Settings
2. Use the and buttons to select the Install Settings entry and then
press the
ENT
button.
energy production
Adj. would effect
Warning:
3. This function is protected with password 5555.
Use the and buttons to set the individual numerals.
Press the
ENT
button to conrm a numeral.
Country
Insulation
4. Use the buttons and to select the entry Inverter ID and press the
ENT
button.
ID=001
Setting ID:
5. Use the and buttons to congure the value and then press the
ENT
button.