Chapter 13 CANopen Overview |C200 Series
13-25
Display
Fault code Description
CANopen
fault code
CANopen
fault
register
(bit 0~7)
EoL2
Thermal relay 2
Fault
cE1
Modbus CMD err
Fault
0036H Illegal function code 7500H 4
Thermal relay 2
Fault
cE2
Modbus ADDR err
Fault
0037H Illegal data address (00H to 254H) 7500H 4
Thermal relay 2
Fault
cE3
Modbus DATA err
Fault
0038H Illegal data value 7500H 4
Thermal relay 2
Fault
cE4
Modbus slave FLT
Fault
0039H Data is written to read-only address 7500H 4
Thermal relay 2
Fault
cE10
Modbus time out
Fault
003AH Modbus transmission timeout. 7500H 4
Thermal relay 2
Fault
cP10
Keypad time out
Fault
003BH Keypad transmission timeout. 7500H 4
Thermal relay 2
Fault
bF
Braking fault
Fault
003CH Brake resistor fault 7110H 4
Thermal relay 2
Fault
ydc
Y-delta connect
Fault
003DH Motor Y-Δ switch error 3330H 2
Thermal relay 2
Fault
dEb
Dec. Energy back
Fault
003EH Energy regeneration when decelerating 3320H 2
Thermal relay 2
Fault
oSL
Over slip Error
Fault
003FH
Overslip error. Slip exceeds Pr.05.26
limit and slip duration exceeds Pr.05.27
setting.
FF00H 7
Thermal relay 2
Fault
ovU
Over volt. Unknow
Fault
Thermal relay 2
Fault
ocU
Unknow Over Apm
Fault
0042H Over current caused by unknown reason 2310H 1