Chapter 11 Description of Parameter Settings|C200 Series
11-8
11-14
IGBT
&
PWM
M
+
-
+
06-12 11-35
+
ASR
11-00 B it 0=0
11-00 B it 0=1
11-06~11-11
11-03~11-05
11-21/11-22
10-00
~
10-02
Encoder
Motor 1
01-01
01-02
05-01
~
05-09
Motor1
01-35
01-36
05-13
~
05-21
no offset
by Pr.03-00
actual frequency
Current feedback
Current
control
Current
measure
flux weakening curve
lq
command
ld command
by Pr.11-29
by multi-function input
Torque command
11-34
11-36 or 00-20
Speed limit or command
Torque limit
11-17~11-20
speed/torque
mode switch
Reserved
Reserved
Load Selection
Factory Setting: 0
Settings
0: Normal load
1: Heavy load
Normal duty: over load, rated output current 160% in 3 second. Please refer to Pr.00-17 for the
setting of carrier wave. Refer to chapter specifications or Pr.00-01 for the rated current.
Heavy duty: over load, rated output current 180% in 3 second. Please refer to Pr.00-17 for the
setting of carrier wave. Refer to chapter specifications or Pr.00-01 for the rated current.
Carrier Frequency
Factory setting: Table below
Settings
215kHz
This parameter determinates the PWM carrier frequency of the AC motor drive.
230V Series 460V Series
Models 1-Phase 0.4-2.2kW 3-Phase 0.4-3.7 kW 3-Phase 0.75-7.5kW
Setting Range 02~15kHz 02~15kHz
Normal Duty Factory Setting 8kHz 8kHz
Heavy Duty Factory Setting 2kHz 2kHz