Chapter 11 Description of Parameter Settings|C200 Series
11-38
Factory Setting: 60.00/50.00
Settings 0.00~600.00Hz
The Width of the Desired Frequency Attained 1
Factory Setting: 2.00
Settings 0.00~600.00Hz
Desired Frequency Attained 2
Factory Setting: 60.00/50.00
Settings 0.00~600.00Hz
The Width of the Desired Frequency Attained 2
Factory Setting: 2.00
Settings 0.00~600.00Hz
Once output frequency reaches desired frequency and the corresponding multi-function output
terminal is set to 3 or 4 (Pr.02-13, 02-14, 02-36, and 02-37), this multi-function output terminal will
be ON.
02-13,
02-14,
02-36,
02-37,
Fcmd=60Hz
02-21=10Hz
02-22=2Hz
02-23=40Hz
02-24=2Hz
H
38Hz
40Hz
42Hz
10Hz
12Hz
8Hz
T
=3
02-13,
02-14,
02-36,
02-37,
=4
~
Reserved
Brake Delay Time
Factory Setting: 0.000
Settings 0.000~65.000 sec
When the AC motor drive runs after Pr.02-32 delay time, the corresponding multi-function output
terminal (12: mechanical brake release) will be ON. It is recommended to use this function with DC
brake.