Chapter 11 Description of Parameter Settings|C200 Series
11-39
RUN
STOP
A
B=A
Multi-function output
(mechanical brake release)
Pr.02-11 to 02-14=d12
Output
frequency
DC brake
07-02
DC brake
time during
start-up
07-03
DC brake
time during
stopping
Mechanical brake
02-32 brake delay time
bounce time of mech anical brake
RUN/STOP
braked
release
frequency
command
braked
DC brake
Time
If this parameter is used without DC brake, it will be invalid. Refer to the following operation timing.
Multi-function output
(mechanical brake
release)
Pr.02-11 to 02-14=d12
RUN
STOP
A
B=A
zero
speed
zero
speed
Time
frequency
command
output
frequency
RUN/STOP
mechanical brake
brake
brake
release
Output Current Level Setting for Multi-function Output Terminals
Factory Setting: 0
Settings 0~100%
When output current is higher or equal to Pr.02-33, it will activate multi-function output terminal
(Pr.02-13, 02-14, 02-16, and 02-17 is set to 27).
When output current is lower than Pr.02-33, it will activate multi-function output terminal (Pr.02-13,
02-14, 02-16, 02-17 is set to 28).