Chapter 11 Description of Parameter Settings|C200 Series
11-40
Output Boundary for Multi-function Output Terminals
Factory Setting: 0.00
Settings 0.00~60.00Hz
When output frequency is higher than Pr.02-34, it will activate the multi-function terminal (Pr.02-13,
02-14, 02-16, 02-17 is set to 29).
When output frequency is lower than Pr.02-34, it will activate the multi-function terminal (Pr.02-13,
02-14, 02-16, 02-17 is set to 30).
External Operation Control Selection after Reset and Activate
Factory Setting: 0
Settings 0: Disable
1: Drive runs if the run command still exists after reset or re-boots.
Setting 1:
Status 1: After the drive is powered on and the external terminal for RUN keeps ON, the drive will
run.
Status 2: After clearing fault once a fault is detected and the external terminal for RUN keeps ON,
the drive can run after pressing RESET key.
~
Reserved
Zero-speed Level of Motor
Factory Setting: 0
Settings 0~65535 rpm
This parameter should be used with the multi-function output terminals (set to 43). It needs to be
used with PG cared and motor with encoder feedback.
This parameter is used to set the level of motor zero-speed. When the actual speed is lower than
this setting, the corresponding multi-function output terminal 43 will be ON as shown as follows.
02-47
MO=d43
actual motor
speed
Time
Max. Frequency of Resolution Switch
Factory Setting: 60.00
Settings 0.00~600.00Hz
Switch the delay time of Max. output frequency
Factory Setting: 0.000