Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-02-21
Settings Functions Descriptions
52
Output control for
communication cards
Control the output through communication cards (CMC-EIP01,
CMC-PN01 and CMC-DN01)
Physical
terminal
Setting of
related
parameters
Attribute
Corresponding
Address
RY1 Pr.02-13 = 52 RW The bit0 of 2640H
RY2 Pr.02-14 = 52 RW The bit1 of 2640H
MO1 Pr.02-16 = 52 RW The bit3 of 2640H
MO2 Pr.02-17 = 52 RW The bit4 of 2640H
MO10 or RA10 Pr.02-36 = 51 RW The bit5 of 2640H
MO11 or RA11 Pr.02-37 = 51 RW The bit6 of 2640H
RA12 Pr.02-38 = 51 RW The bit7 of 2640H
RA13 Pr.02-39 = 51 RW The bit8 of 2640H
RA14 Pr.02-40 = 51 RW The bit9 of 2640H
RA15 Pr.02-41= 51 RW The bit10 of 2640H
65
Output for both
CANopen and RS-485
To control output of CANopen & InnerCOM internal
communication.
66 SO output logic A (N.O.)
Status of the
drive
Status of safety output
Status A (MOx=66) Status B (MOx=68)
Normal Broken circuit (Open) Short circuit (Close)
STO Short circuit (Close) Broken circuit (Open)
STL1–STL3 Short circuit (Close) Broken circuit (Open)
68 SO output logic B (N.C.)
67
Analog input level
reached
The multi-function output terminals operate when the analog input
level is between the high level and the low level.
Pr.03-44: Select one of the analog input channels (AVI, ACI and
AUI) to be compared.
Pr.03-45: The high level for the analog input, default is 50%.
Pr.03-46: The low level for the analog input, default is 10%.
If analog input > Pr.03-45, the multi-function output terminal
operates. If analog input < Pr.03-46, the multi-function output
terminal stops output.
70
Fan warning detection
output
The terminal works when the internal fan warning activates
75
Forward running status
MO=75 activates (ON) when the drive runs in forward.
MO=76 activates (ON) when the drive runs in reverse.
When the drive is in stop status, MO=75 and MO=76 deactivates
(OFF).