Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-02-22
Settings Functions Descriptions
76
Reverse running status
Multi-function output (MO) terminal
25
Forward command
26
Reverse command
75
Forward
running status
76
Reverse
running status
Drive runs in
FWD
ON OFF ON OFF
Drive runs in
REV
OFF ON OFF ON
Drive stops
The drive runs in
forward and stops.
The "FWD" light
on the panel is in a
steady ON status,
and MO=25
remains ON.
The drive runs in
reverse and stops.
The "REV" light on
the panel is in a
steady ON status,
and MO=26
remains ON.
OFF OFF
When the drive is in stop status, either
MO=25 or MO=26 activates (ON).
When the drive is in stop
status, both MO=75 and
MO=76 deactivate (OFF).
Example: Crane Application
It is recommended to be used with Dwell function as shown in the following:
When using the crane application and MOx = 42, Pr.02-34 must be larger than Pr.02-58; Pr.02-
33 must be larger than Pr.02-57.