Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-02-25
Once the output speed (frequency) reaches desired speed (frequency), if the corresponding multi-
function output terminal is set to 3–4 (Pr.02-13, Pr.02-14, Pr.02-36 and Pr.02-37), this multi-
function output terminal is “closed”.
02-32
Brake Delay Time
Default: 0.000
Settings 0.000–65.000 sec.
When the AC motor drive runs after the setting delay time of Pr.02-32, the corresponding multi-
function output terminal (12: mechanical brake release) is “closed”. This function must be used
with DC brake.