Chapter 12 Description of Parameter SettingsME300 
 
12.1-03-18 
  When Pr.03-28 ≠ 1, the ACI setting is 0–20 mA or 4–20 mA and the unit is current (mA). 
  When  you  set  the  analog  input  ACI  to  the  Frequency  command,  100%  corresponds  to  Fmax 
(Pr.01-00 Maximum Operation Frequency).     
  The output % becomes 0% when the ACI input value is lower than lowest point setting.   
For example:   
If Pr.03-57 = 2 mA; Pr.03-58 = 10%, then the output becomes 0% when the AVI input is ≤ 2 mA. 
If the ACI input swings between 2 mA and 2.1 mA, the drive’s output frequency oscillates 
between 0% and 10%. 
 
 
AVI Voltage Lowest Point 
 
 
 
Default: 0.00
 
 
Settings  0.00–10.00 V 
 
 
AVI Voltage Proportional Lowest Point 
 
 
 
Default: 0.00
 
 
Settings  -100.00–100.00% 
 
 
AVI Voltage Mid-point     
 
 
 
Default: 5.00
 
 
Settings  0.00–10.00 V 
 
AVI Voltage Proportional Mid-point 
 
 
 
Default: 50.00
 
 
Settings  -100.00–100.00% 
 
 
AVI Voltage Highest Point 
 
 
 
Default: 10.00
 
 
Settings  0.00–10.00 V 
 
 
AVI Voltage Proportional Highest Point   
 
 
 
Default: 100.00
 
 
Settings  -100.00–100.00%
 
  When you set the positive voltage AVI to the Frequency command, 100% corresponds to Fmax 
(Pr.01-00 Maximum Operation Frequency) and the motor runs in the forward direction. 
  The  requirement  for  these  three  parameters  (Pr.03-63,  Pr.03-65  and  Pr.03-67)  is  Pr.03-63  < 
Pr.03-65 < Pr.03-67. The values for three proportional points (Pr.03-64, Pr.03-66 and Pr.03-68) 
have no limits. There is a linear calculation between two points. 
  The output % becomes 0% when the positive voltage AVI input value is lower than lowest point 
setting.   
For example:   
If Pr.03-63 = 1 V; Pr.03-64 = 10%, then the output becomes 0% when the AVI input is ≤ 1 V.   
If the AVI input swings between 1 V and 1.1 V, the drive’s output frequency oscillates between 
0% and 10%.