Chapter 12 Description of Parameter SettingsME300 
 
 
12.1-08-6 
Parallel connection 
 
 
Feedback Signal Detection Time 
 
 
 
Default: 0.0
 
 
Settings  0.0–3600.0 sec.
 
  Pr.08-08 is valid only for Pr.03-28=2 (4–20 mA). 
  This parameter sets the detection time for abnormal PID signal feedback. Setting the detection 
time to 0.0 disables the detection function. 
 
 
Feedback Signal Fault Treatment 
 
   
 
Default: 0
 
 
Settings  0: Warn and continue operation
 
   
1: Warn and ramp to stop
 
   
2: Warn and coast to stop
 
   
3: Warn and operate at last frequency 
 
  This parameter is valid only for Pr.03-28=2 (4–20 mA).. 
  The AC motor drive acts when the analog PID feedback is abnormal. 
 
 
Sleep Frequency 
 
 
  Default: 0.00 
  Settings  0.00–599.00 Hz 
  Determines the sleep frequency, and if the sleep time and the wake-up frequency are enabled or 
disabled.   
Pr.08-10 = 0: Disabled 
Pr.08-10 = ≠ 0: Enabled