Chapter  10  Digital  KeypadCP2000 
 
 
10-33
File Copy Setting Fault Description: 
These faults will happen when KPC-CC01 cannot perform the command after clicking the Enter button in 
copy function.
 
 
LCD Display *  Description  Corrective Actions 
 
Parameter and file are read only 
The property of the parameter / file is read-only and 
cannot be written to. 
1.  Verify the specification on the user manual. 
If the solution above doesn’t work, contact your local 
authorized dealer. 
 
Fail to write parameter and file   
An error occurred while writing to a parameter / file. 
1. Verify if there’s any problem on the Flash IC. 
2. Shut down the system, wait for ten minutes, and 
then power on again the system. 
If none of the solution above work, contact your local 
authorized dealer. 
 
AC drive is in operating status   
A setting cannot be made while motor drive is in 
operation. 
1. Verify if the drive is not in operation. 
If the solution above doesn’t work, contact your local 
authorized dealer.
 
 
AC drive parameter is locked   
A setting cannot be made because a parameter is 
locked. 
1. Verify if the parameter is locked or not. If it is locked, 
unlock it and try to set up the parameter again. 
If the solution above doesn’t work, contact your local 
authorized dealer.
 
 
AC drive parameter changing 
A setting cannot be made because a parameter is 
being modified. 
1. Verify if the parameter is being modified. If it is not 
being modified, try to set up that parameter again. 
If the solution above doesn’t work, contact your local 
authorized dealer.
 
 
Fault code   
A setting cannot be made because an error has 
occurred on the motor drive. 
1. Verify if there’s any error occurred on the motor 
drive. If there isn’t any error, try to make the setting 
again. 
If the solution above doesn’t work, contact your local 
authorized dealer.   
 
Warning code   
A setting cannot be made because of a warning 
message given to the motor drive. 
1. Verify if there’s any warning message given to the 
motor drive. 
If the solution above doesn’t work, contact your local 
authorized dealer.   
 
File type dismatch 
The copied data are not the same type, so the setting 
cannot be made. 
1. Verify if the products’ serial numbers need to be 
copied fall in the category. If they are in the same 
category, try to make the setting again. 
If the solution above doesn’t work, contact your 
authorized dealer.