Chapter 11 Summary of Parameter SettingsCP2000 
 
11-24 
  Pr.  Parameter Name  Setting Range  Default 
  06-06 
Over-torque detection selection 
(OT1) 
0: No function 
1: Continue operation after over-torque detection 
during constant speed operation 
2: Stop after over-torque detection during constant 
speed operation 
3: Continue operation after over-torque detection 
during RUN 
4: Stop after over-torque detection during RUN 
0 
  06-07  Over-torque detection level (OT1) 
10–200% (100% corresponds to the light-load rated 
current of the drive)
 
120 
  06-08  Over-torque detection time (OT1)  0.0–60.0 sec.  0.1 
  06-09 
Over-torque detection selection 
(OT2) 
0: No function 
1: Continue operation after over-torque detection 
during constant speed operation 
2: Stop after over-torque detection during constant 
speed operation 
3: Continue operation after over-torque detection 
during RUN 
4: Stop after over-torque detection during RUN
 
0 
  06-10  Over-torque detection level (OT2) 
10–200% (100% corresponds to the light-load rated 
current of the drive)
 
120 
  06-11  Over-torque detection time (OT2)  0.0–60.0 sec.  0.1 
  06-13 
Electronic thermal relay selection 
1 (Motor 1) 
0: Inverter motor (with external forced cooling) 
1: Standard motor (motor with fan on the shaft) 
2: Disable
 
2 
  06-14 
Electronic thermal relay action 
time 1 (Motor 1) 
30.0–600.0 sec.  60.0 
  06-15 
Temperature level over-heat (OH) 
warning 
0.0–110.0°C  105.0 
  06-16 
Stall prevention limit level 
(Weak magnetic area current stall 
prevention level) 
0–100% (Pr.06-03, Pr.06-04)  50 
  06-17  Fault record 1    0: No fault record  0 
  06-18  Fault record 2  1: Over-current during acceleration (ocA) 0 
  06-19  Fault record 3  2: Over-current during deceleration (ocd) 0 
  06-20  Fault record 4  3: Over-current during constant speed (ocn)  0 
  06-21  Fault record 5  4: Ground fault (GFF)  0 
  06-22  Fault record 6  5: IGBT short-circuit (occ)  0 
      6: Over-current at stop (ocS)   
      7: Over-voltage during acceleration (ovA)   
      8: Over-voltage during deceleration (ovd)   
      9: Over-voltage during constant speed (ovn)   
      10: Over-voltage at stop (ovS)   
      11: Low-voltage during acceleration (LvA)   
      12: Low-voltage during deceleration (Lvd)   
      13: Low-voltage during constant speed (Lvn)   
      14: Low-voltage at stop (LvS)   
      15: Phase loss protection (OrP)