Chapter 12 Description of Parameter SettingsMS300 (High Speed Model) 
 
12-06-1 
06 Protection Parameters (1)         This parameter can be set during operation. 
 
 
Low Voltage Level 
 
 
 Factory Setting: 
 Settings 230 V: 150.0~220.0 VDC    180.0 
 
 
460 V: 300.0~440.0 VDC  360.0 
  This parameter is used to set the Low Voltage (LV) level. When the DC-BUS voltage is lower than 
Pr. 06-00, drive will stop output and free to stop. 
  If LV fault is triggered during operation, the drive will stop output and free to stop. There are three 
LV faults, LvA (LV during acceleration), Lvd (LV during deceleration), and Lvn (LV in constant 
speed) which will be triggered according to the status of acceleration / deceleration. These faults 
need to be RESET manually to restart the drive, while setting restart after momentary power off 
function (Refer to Pr. 07-06 and Pr. 07-07), the drive will restart automatically. 
  If LV fault is triggered when the drive is in stop status, the drive will display LvS (LV during stop), 
which will not be recorded, and the drive will restart automatically when input voltage is higher 
than LV level 30V (230V series) or 60V (460V series). 
LV
Pr. 06-00
30V(60V)
input voltage
 
 
 
Over-voltage Stall Prevention 
   Settings  0: Disabled         Factory Setting: 
     230 V: 0.0~450.0 VDC                   380.0 
     460 V: 0.0~900.0 VDC                   760.0 
  When Pr. 06-01 is set to 0.0, the over-voltage stall prevention function is disabled (connected with 
braking unit or braking resistor). This setting is recommended when braking units or resistors are 
connected to the drive. 
  When the setting value is not 0.0, the over-voltage stall prevention is activated. This setting 
should refer to power supply system and loading. If the setting is too low, then over-voltage stall 
prevention will be easily activated, which may increase deceleration time. 
  Related parameters: Pr. 01-13, Pr. 01-15, Pr. 01-17, Pr. 01-19 Decel. Time 1~4, Pr. 02-13 
Multi-function output (Relay), Pr. 02-16~Pr. 02-17 Multi-function output (MO1, 2), and   
Pr. 06-02 Selection for over-voltage stall prevention. 
 
 
Selection for Over-voltage Stall Prevention   
 
 
  Factory Setting: 0 
  Settings  0: Traditional over-voltage stall prevention 
    1: Smart over-voltage stall prevention