Chapter 13 Warning CodesMS300 (High Speed Model) 
 
13-2
ID No.  Display  Descriptions 
9 
 
IGBT is over-heated than protection level 1~10 HP: 90 
o
C 
Corrective Actions 
  Ensure that the ambient temperature falls within the specified 
temperature range. 
  Make sure that the ventilation holes are not obstructed. 
  Remove any foreign objects from the heat sink and check for possible 
dirty in heat sink. 
  Check the fan and clean it. 
  Provide enough spacing for adequate ventilation. 
11 
 
PID feedback loss 
12 
 
ACI signal loss   
When Pr. 03-19 is set to 1 or 2.     
13 
 
Low current 
15 
 
PG feedback error 
16 
 
PG feedback loss 
17 
 
Over-speed warning 
18 
 
Over speed deviation warning 
20 
 
When the output current exceeds the over-torque detection level (Pr. 06-07 
or Pr. 06-10) and also exceeds Pr. 06-08 or Pr. 06-11, when Pr. 06-06 or   
Pr. 06-09 is set as 1 or 3, it will display warning without abnormal record; 
when Pr. 06-06 or 06-09 is set as 2 or 4, it will display error, stop running 
and there will be an abnormal record.   
Corrective Actions 
  Check if motor is overloaded. 
  Check Pr. 05-01 motor rated current is correct or not. 
  Increase motor capacity. 
21 
 
22 
 
Motor over-heating 
24 
 
Over slip 
25 
 
Auto tuning processing