Chapter 16 PLC Function ApplicationsC2000 Plus 
 
16-115 
API  
 
LD※ 
 
S1 S2
 
Contact form compare LD* 
224– 
230 
 
D  
 
  
 
 
Bit device    Word device   
16-bit command  (5 STEP) 
LD※ 
Continuous 
execution type 
-  - 
 
32-bit command  (9 STEP) 
DLD※ 
Continuous 
execution type 
-  - 
 
Flag signal: none   
X Y M K  H KnX KnY KnM T  C  D 
S1    * * * * * * * * 
S2    * * * * * * * * 
Notes on operand usage:  ※:=、>、<、<>、≦、≧ 
Please refer to the function specifications table for each device in 
series for the scope of device usage 
 
 
  S
1
: data source device 1. S
2
: data source device 2.   
  This command compares the content of S
1
 and S
2
. Taking API 224 (LD=) as an 
example, this command will be activated when the result of comparison is "equal," 
and will not be activated when the result is "unequal."   
  The LD* can be used while directly connected with the busbar   
API No.  16-bit commands 32-bit commands 
Conditions for 
activation 
Conditions for 
inactivation 
224 
LD=  DLD= 
S
1 
=  S
2
 
S
1 
≠ S
2
 
225 
LD>  DLD> 
S
1 
>  S
2
  S
1 
≦  S
2
 
226 
LD<  DLD< 
S
1 
<  S
2
  S
1 
≧  S
2
 
228 
LD<>  DLD<> 
S
1 
≠ S
2
 
S
1 
=  S
2
 
229 
LD<=  DLD<= 
S
1 
≦  S
2
  S
1 
>  S
2
 
230 
LD>=  DLD>= 
S
1 
≧  S
2
  S
1 
<  S
2
 
 
 
  When the content of C10 is equal to K200, Y10=On.   
  When the content of D200 is greater than K-30, and X1=On, Y11=On and remains 
in that state.   
LD=
K200 C10
DLD>
K678493 C20
M3
Y10
LD>
D200 K-30
SET Y11
M50
X1