Chapter 11 Summary of Parameter SettingsC2000 Plus
11-28
05 Motor Parameters
Pr. Parameter Name Setting Range Default
05-00 Motor Parameter Auto-Tuning
0: No function
1: Simple rolling auto-tuning for induction motor (IM)
2: Static auto-tuning for induction motor (IM)
4: Dynamic test for PM magnetic pole
(with the running in forward direction)
5: Rolling auto-tuning for PM (IPM / SPM)
6: Advanced rolling auto-tuning for IM
11: Static auto-tuning for SynRM
12: FOC sensorless inertia estimation
13: Static auto-tuning for PM
0
05-01
Full-Load Current for Induction
Motor 1 (A)
Depending on the model power
Depending
on the
model
power
05-02
Rated Power for Induction Motor
1 (kW)
0.00–655.35 kW
Depending
on the
model
power
05-03
Rated Speed for Induction Motor
1 (rpm)
0–xxxx rpm
(Depending on the motor’s number of poles)
Depending
on the
motor’s
number of
poles
05-04
Number of Poles for Induction
Motor 1
2–64 4
05-05
No-Load Current for Induction
Motor 1 (A)
0.00–Pr.05-01 default
Depending
on the
model
power
05-06
Stator Resistance (Rs) for
Induction Motor 1
0.000–65.535
Depending
on the
model
power
05-07
Rotor Resistance (Rr) for
Induction Motor 1
0.000–65.535
Depending
on the
model
power
05-08
Magnetizing Inductance (Lm) for
Induction Motor 1
0.0–6553.5 mH
Depending
on the
model
power
05-09
Stator Inductance (Lx) for
Induction Motor 1
0.0–6553.5 mH
Depending
on the
model
power
05-13
Full-Load Current for Induction
Motor 2 (A)
Depending on the model power
Depending
on the
model
power
05-14
Rated Power for Induction Motor
2 (kW)
0.00–655.35 kW
Depending
on the
model
power
05-15
Rated Speed for Induction Motor
2 (rpm)
0–xxxx rpm
(Depending on the motor’s number of poles)
Depending
on the
motor’s
number of
poles
05-16
Number of Poles for Induction
Motor 2
2–64 4