Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-03-23
When Pr.03-50 = 0, all analog input signal is calculated by bias and gain.
When Pr.03-50 = 1, AVI calculates by frequency and voltage / current (Pr.03-51–03-56), other
analog input signal calculates by bias and gain.
When Pr.03-50 = 2, ACI consulates by frequency and voltage / current (Pr.03-57–03-62), other
analog input signal calculates by bias and gain.
When Pr.03-50 = 3, AVI and ACI calculate by frequency and voltage/ current (Pr.03-51–03-62),
other analog input signal calculates by bias and gain.
When Pr.03-50 = 4, AVI calculates by frequency and voltage / current (Pr.03-63–03-74), other
analog input signal calculates by bias and gain.
When Pr.03-50 = 5, AVI and AUI calculate by frequency and voltage / current (Pr.03-51–03-56
and 03-63–03-74), other analog input signal calculates by bias and gain.
When Pr.03-50 = 6, ACI and AVI calculate by frequency and voltage / current (Pr.03-57–03-74),
other analog input signal calculates by bias and gain.
When Pr.03-50 = 7, all analog input signal calculates by frequency and voltage / current (Pr.03-
51–03-74).
03-51
AVI Lowest Point
Default:
Settings Pr.03-28 = 0, 0.00–10.00 V 0.00
Pr.03-28 = 1, 0.00–20.00 mA 0.00
Pr.03-28 = 2, 4.00–20.00 mA 4.00
03-52
AVI Proportional Lowest Point
Default:
Settings -100.00–100.00% 0.00
03-53
AVI Mid-Point
Default:
Settings Pr.03-28 = 0, 0.00–10.00 V 5.00
Pr.03-28 = 1, 0.00–20.00 mA 10.00
Pr.03-28 = 2, 4.00–20.00 mA 12.00
03-54
AVI Proportional Mid-Point
Default:
Settings -100.00–100.00% 50.00
03-55
AVI Highest Point
Default:
Settings Pr.03-28 = 0, 0.00–10.00 V 10.00
Pr.03-28 = 1, 0.00–20.00 mA 20.00
Pr.03-28 = 2, 4.00–20.00 mA 20.00
03-56
AVI Proportional Highest Point
Default:
Settings -100.00–100.00% 100.00
When Pr.03-28 = 0, the AVI setting is 0–10 V and the unit is in voltage (V).
When Pr.03-28 0, the AVI setting is 0–20 mA or 4–20 mA and the unit is in current (mA).