Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-06-15
Fault Code 
bit0  bit1  bit2  bit3  bit4  bit5  bit6 
current  Volt.  OL  SYS  FBK  EXI  CE 
0: No fault record 
   
1: Over-current during acceleration (ocA) 
●
 
 
2: Over-current during deceleration (ocd) 
●
 
 
3: Over-current during steady operation (ocn) 
●
 
 
4: Ground fault (GFF) 
●
 
 
5: IGBT short circuit between upper bridge and 
lower bridge (occ) 
●
 
 
6: Over-current at stop (ocS) 
●
 
 
7: Over-voltage during acceleration (ovA) 
 
● 
 
8: Over-voltage during deceleration (ovd) 
 
● 
 
9: Over-voltage at constant speed (ovn) 
 
● 
 
10: Over-voltage at stop (ovS) 
 
● 
 
11: Low-voltage during acceleration (LvA) 
 
● 
 
12: Low-voltage during deceleration (Lvd) 
 
● 
 
13: Low-voltage at constant speed (Lvn) 
 
● 
 
14: Low-voltage at stop (LvS) 
 
● 
 
15: Phase loss protection (OrP) 
 
● 
 
16: IGBT overheating (oH1)   
 
● 
 
17: Heatsink overheating (oH2)   
 
● 
 
18: IGBT temperature detection failure (tH1o) 
 
● 
 
19: Capacitor hardware error (tH2o ) 
 
● 
 
21: Over load (oL) 
 
● 
 
22: Electronic thermal relay 1 protection (EoL1) 
 
● 
 
23: Electronic thermal relay 2 protection (EoL2) 
 
● 
 
24: Motor overheating (oH3) (PTC / PT100) 
 
● 
 
25: Interrupt error (INTR) 
 
 
●
     
26: Over torque 1 (ot1) 
 
● 
 
27: Over torque 2 (ot2) 
 
● 
 
28: Under current (uC) 
●
 
 
29: Limit error (LiT) 
   
● 
 
30: EEPROM write error (cF1) 
  
● 
 
31: EEPROM read error (cF2) 
  
● 
 
33: U-phase error (cd1) 
  
● 
 
34: V-phase error (cd2) 
  
● 
 
35: W-phase error (cd3) 
  
● 
 
36: cc (current clamp) hardware error (Hd0) 
  
● 
 
37: oc (over-current) hardware error (Hd1) 
  
● 
 
38: ov (over-voltage) hardware error (Hd2) 
  
●