Chapter 12 Description of Parameter SettingsC2000 Plus 
 
 
12.2-33
 IPM Sensorless adjustment procedure   
I. IPM Sensorless adjustment flowchart 
1. Parameter Reset
Pr.00-02=9 or 10
2. Pr.05-33 Motor type=2 (IPM)
FOC Sensorless control 
( For IPM motor)
3. Motor Parameter Setting
Pr.01-01 Rated Frequency
Pr.01-02 Rated Voltage
Pr.05-34 Full-load Current
Pr.05-35 Rated Power
Pr.05-36 Rated Rotor Speed
Pr.05-37 Motor Poles
4. Motor Parameter Auto-Tuning
Pr.05-00=5
(PM parameters dynamic measuring)
Or Pr.05-00=13
(PM parameters static measuring)
Press 'RUN’
PM FOC Sensorless 
Adjustment Procedure
(Ver.3.05 and later)
Motor auto-tuning 
successful?
1. AUE auto-tuning error
2. Measured resistance, 
inductance or back 
EMF error
Check Motor Parameters
Pr.05-39 Rs stator resistance
Pr.05-40 Permanent magnet 
motor Ld
Pr.05-41 Permanent magnet 
motor Lq
Pr.05-43 Ke parameter
6. Re-power after Power Off
YES
7. Initial Angle Detection
Pr.10-53 angle detection
2:High frequency injection
PM FOC Sensorless Control
The initial angle is only 
detected by “2” high 
frequency injection, and cannot 
be changed.
NO
8. No-load 
Running
5. Set Control Mode
Pr.00-10=0 Speed mode
Pr.00-11=7 FOC Sensorless control
 
 
NOTE: The number marked on the procedure corresponds to the number of following adjustment 
explanations)