Chapter 14 Fault Codes and DescriptionsME300 
 
14-18
ID No.  Display on LCM Keypad  Fault Name  Fault Descriptions 
52 
 
Password is locked 
(Pcod) 
Entering the wrong password three consecutive times 
Action and Reset 
Action level  Entering the wrong password three consecutive times 
Action time  Immediately act 
Fault treatment parameter  N/A 
Reset method  Manual reset 
Reset condition  Power-off 
Record  Yes 
Cause  Corrective Actions 
Incorrect password input through 
Pr.00-07 
1.  Input the correct password after rebooting the motor drive. 
2.  If you forget the password, enter 9999. 
3.  Press ENTER, and then enter 9999 again.   
4.  You must finish pressing ENTER within 10 seconds. If not, you must repeat 
the  entering.  After  you  successfully  unlock  the  password,  the  parameter 
settings return to the default. 
 
ID No.  Display on LCM Keypad  Fault Name  Fault Descriptions 
54 
 
Illegal command   
(CE1) 
Communication command is illegal 
Action and Reset 
Action level  When the function code is not 03, 06, 10, or 63. 
Action time  Immediately act 
Fault treatment parameter  N/A 
Reset method  Manual reset 
Reset condition  Immediately reset 
Record  No 
Cause  Corrective Actions 
Incorrect communication 
command from the upper unit 
Check if the communication command is correct. 
Malfunction caused by interference 
Verify the wiring and grounding of the communication circuit. It is recommended 
to separate the communication circuit from the main circuit, or wire in 90 degree 
for effective anti-interference performance. 
Different communication setting 
from the upper unit 
Check if the setting for Pr.09-02 is the same as the setting for the upper unit. 
Disconnection or bad connection 
of the cable 
Check the cable and replace it if necessary. 
 
ID No.  Display on LCM Keypad  Fault Name  Fault Descriptions 
55 
 
Illegal data address 
(CE2) 
Data address is illegal. 
Action and Reset 
Action level  When the data address is correct. 
Action time  Immediately act 
Fault treatment parameter  N/A 
Reset method  Manual reset 
Reset condition  Immediately reset 
Record  No 
Cause  Corrective Actions 
Incorrect communication 
command from the upper unit 
Check if the communication command is correct. 
Malfunction caused by interference 
Verify the wiring and grounding of the communication circuit. It is recommended 
to separate the communication circuit from the main circuit, or wire in 90 degree 
for effective anti-interference performance. 
Different communication setting 
from the upper unit 
Check if the setting for Pr.09-02 is the same as the setting for the upper unit. 
Disconnection or bad connection 
of the cable 
Check the cable and replace it if necessary.