Chapter 12 Descriptions of Parameter SettingsMS300
389
07-15
Dwell Time at Acceleration
Default: 0.00
Settings
0.00–600.00 sec.
07-17
Dwell Time at Deceleration
Default: 0.00
Settings
0.00–600.00 sec.
07-16
Dwell Frequency at Acceleration
Default: 0.00
Settings
0.00–599.00 Hz
07-18
Dwell Frequency at Deceleration
Default: 0.00
Settings
0.00–599.00 Hz
In heavy load situations, the Dwell temporarily maintains stable output frequency. Use this
parameter for cranes, elevators, and so on.
For heavy load applications, use Pr.07-15–Pr.07-18 to avoid OV or OC protection.