EasyManuals Logo

Delta VFD9A0MS43ANSAA User Manual

Delta VFD9A0MS43ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #503 background imageLoading...
Page #503 background image
Chapter 13 Warning CodesMS300
494
ID No.
Display on LCD Keypad
Warning Name
Description
28
Output phase loss
(oPHL)
Output phase loss of the drive
Action and Reset
Action Condition
Pr.06-47
Action Time
N/A
Warning Setting Parameter
Pr.06-45
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
Reset Method
If Pr.06-45 is set to 0, the oPHL warning automatically clears after the drive
stops.
Reset Condition
N/A
Record
N/A
Cause
Corrective Actions
Unbalanced three-phase
impedance of the motor
Replace the motor.
Check if the wiring is incorrect
Check the cable.
Replace the cable.
Check if the motor is a single-
phase motor
Choose a three-phase motor.
Check if the current sensor is
broken
Check if the control board cable is loose. If yes, reconnect the cable and run the
drive to test. If the error still occurs, return to the factory for repair.
Check if the three-phase current is balanced with a current clamp meter. If the
current is balanced and the oPHL error still shows on the display, return to the
factory for repair.
Check if capacity of the drive is
larger than the motor
Choose a drive’s capacity matches a motor’s.

Table of Contents

Other manuals for Delta VFD9A0MS43ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD9A0MS43ANSAA and is the answer not in the manual?

Delta VFD9A0MS43ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD9A0MS43ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals