EasyManuals Logo

Delta VFD9A0MS43ANSAA User Manual

Delta VFD9A0MS43ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #511 background imageLoading...
Page #511 background image
Chapter 13 Warning CodesMS300
502
ID No.
Display on LCD Keypad
Warning Name
Description
41
CANopen station
address error (CAdn)
CANopen station address error (only supports 1–127)
Action and Reset
Action Condition
CANopen station address error
Action Time
Immediately act when the fault is detected
Warning Setting Parameter
N/A
Reset Method
Manual Reset
Reset Condition
Pr.00-02 = 7
Record
When Pr.00-21 ≠ 3, CAdn is a “Warning”, and the warning is not recorded.
Cause
Corrective Actions
Incorrect setting of CANopen
station address
1. Disable CANopen (Pr.09-36 = 0)
2. Reset CANopen (Pr.00-02 = 7)
3. Reset CANopen station address (Pr.09-36)

Table of Contents

Other manuals for Delta VFD9A0MS43ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD9A0MS43ANSAA and is the answer not in the manual?

Delta VFD9A0MS43ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD9A0MS43ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals