7
ELECTRICAL SCHEMATIC
AIR AND REFRIGERANT FLOW SCHEMATIC
Figure 1 Figure 2
HEAT EXCHANGER
REHEATER
AUX. CONDENSER
AIR OUTLET
SEPARATOR
EVAPORATOR
CHILLER
DRAIN OUTLET
AIR INLET
LIQUID RECEIVER
/ FILTER DRYER
CONSTANT PRESSURE
EXPANSION VALVE
REF. COMPRESSOR
ON/OFF SWITCH
WITH RUNNING LAMP
R
25
6
PTC STARTER
S
M
COMP.
1PH
C
OVERLOAD
PROTECTOR
ENGINEERING DATA
SCFM 10 15
SPECIFICATIONS
Rated Capacity
a
-(scfm) 10 15
Inlet /Outlet Connections - (inches) 3/8 3/8
Dimensions
Height - (inches) 15.4 15.4
Length - (inches) 12.6 12.6
Width - (inches) 12.6 12.6
PowerSupply-(V/Ph/Hz) 115/1/60 115/1/60
RefrigerantCompressorRating-(hp) 1/8 1/7
InputPower-(kW) 0.21 0.24
RefrigerantType
b
R-134a R-134a
MINIMUM - MAXIMUM OPERATING CONDITIONS
Min.-Max.InletAirPressure(compressedairatinlettodryer) 30 - 250 psig 30 - 250 psig
Min.-Max.InletAirTemperature(compressedairatinlettodryer) 40°F - 122°F 40°F - 122°F
Min.-Max.AmbientTemperature 40°F - 113°F 40°F - 113°F
a
Ratingconditionsare100°Finlettemperature,100psiginletpressure,100%inletrelativehumidity,100°Fambienttemperature@60Hz.PerCAGIADF-100
b
Refertodryerdataplateforrefrigerantcharge.