7. 1 95-866610
SPECIFICATIONS
TERMINALS—
UL/CSA rated for 12–26 AWG, 2.51.5 mm
2
wire. Screw
terminal required torque range is 3.55.3 in.-lbs. (0.4-
0.6 N•m).
ELECTRICAL RATING
Open circuit monitoring:
1.0 Amp maximum @ 30 Vdc (resistive).
Open & short circuit monitoring:
1.0 Amp maximum @ 30 Vdc (resistive).
AMBIENT TEMPERATURE RANGE—
Operating: 4F to +257°F (–4C to +125°C).
Storage: 4F to +257°F (40°C to +125°C).
TEMPERATURE PERFORMANCE RANGE—
Refer to the Model Matrix in the “Ordering Information”
section of this manual.
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
THREAD OPTIONS
3/4 inch NPT or M25.
Two or four port models available.
Note:
NEMA 4 / IP66 / IP67 rating requires the use of
IP
washers / IP glands (M25)
.
DIMENSIONS—
See Figure 14.
CERTIFICATION
For complete approval details, refer to the appropriate
Appendix:
Appendix A – FM
Appendix B – CSA
Appendix C – ATEX
Appendix D – IECEx
Appendix E – Additional Approvals
DEVICE REPAIR AND RETURN
Prior to returning devices, contact the nearest local
Detector Electronics office so that a Return Material
Authorization (RMA) number can be assigned. A
written statement describing the malfunction must
accompany the returned device or component to
assist and expedite nding the root cause of the
failure.
Pack the unit properly. Always use sufficient packing
material. Where applicable, use an antistatic bag as
protection from electrostatic discharge.
NOTE
Det-Tronics reserves the right to apply a service
charge for repairing returned product damaged
as a result of improper customer packaging.
Return all equipment via transportation prepaid to the
factory in Minneapolis.
NOTE
It is highly recommended that a spare detector
be kept on hand for eld replacement to ensure
continuous protection.
ORDERING INFORMATION
When ordering, please specify:
Model HD Risk Area Heat Detector with Explosion-Proof
Junction Box
Refer to the Model Matrix for details.
3.46
(8.8)
4.7
(11.9)
2.7
(6.9)
5.2
(13.2)
~10.6
(~26.9)
C2539
3.77
(9.6)
1.28
(3.3)
0.6
(1.5)
3.7
(9.4)
Figure 14—Dimensions of Heat Detector in Inches (cm)