INSTALLATION INSTRUCTIONS AND
HOMEOWNER’S MANUAL
Models:
COND-OCD-09
COND-OCD-12
COND-OCD-18
COND-OCD-24
COND-OCD-30
COND-OCD-36
INSTALLER / SERVICE TECHNICIAN:
Use the information in this manual for the installation / servicing and keep the document near the furnace
for future reference.
Communication wire connected between the indoor and outdoor units must be rated for at least 120VAC,
they are protected by the outdoor unit breaker and must be sized appropriatly.
Do not install any metering device on the indoor coil. The expension valve is located in the outdoor unit.
If a metering device is already installed in the indoor coil, it must be removed.
Both refrigerant lines must be separately insulated in order to avoid condensation and to ensure proper
efficiency.
COND-OCD -09 -12 -18 -24 -30 -36
Liquid line dia (In) 1/4 1/4 1/4 1/4 1/4 1/4
Gas line dia (In) 3/8 1/2 5/8 5/8 5/8 5/8
HOMEOWNER:
Please keep this manual near the furnace for future reference.
CAUTION:
Do not tamper with the unit or its controls. Call a qualified service technician.
Manufactured by:
Dettson Industries Inc.
Sherbrooke, Qc, Canada
www.dettson.com
Printed in Canada on 2020-05-08 X40257 Rev.A
100% recycled paper

Questions and Answers

  • M
    Maria MooreSep 8, 2025
    What does condensor sensor error mean on Dettson Air Conditioner?
    • Z
      zhancockSep 9, 2025
      A condenser sensor error on your Dettson Air Conditioner, which causes the unit to stop, suggests that the sensor is either damaged or disconnected.
  • G
    Grant MitchellSep 12, 2025
    What does discharge sensor error mean on Dettson Air Conditioner?
    • T
      Taylor AlvaradoSep 12, 2025
      A discharge sensor error on your Dettson Air Conditioner, which leads to the unit stopping, indicates that the sensor is either damaged or disconnected.
  • D
    Danny CampbellSep 12, 2025
    What causes compressor desynchronizing in Dettson Air Conditioner?
    • B
      benjamin75Sep 13, 2025
      Compressor desynchronizing in your Dettson Air Conditioner, causing the unit to stop, can be due to IPM protection or overcurrent.
  • J
    Jennifer WalkerSep 14, 2025
    What causes ODU Fan motor failure in Dettson COND-OCD-09 Air Conditioner?
    • F
      frobertsSep 14, 2025
      ODU fan motor failure in your Dettson Air Conditioner, resulting in the unit stopping, can be caused by motor malfunction, a blocked fan, or a disconnected motor.
  • L
    Lindsey CookSep 16, 2025
    What does power protection mean on Dettson COND-OCD-09?
    • K
      Kevin ZimmermanSep 17, 2025
      If your Dettson Air Conditioner is in power protection mode, indicated by 3-minute cycles, it is due to abnormal power supply voltage.